Transformer FLC Calculator
Full Load Current (FLC) Results:
Primary Current (High Side): 0 Amps
Secondary Current (Low Side): 0 Amps
How It Works & Transformer Formulas
Transformer Full Load Current (FLC) calculation depends on apparant power capacity (kVA), system voltage levels, and whether the system configuration is 1-Phase or 3-Phase.
Governing Equations:
3-Phase Full Load Current (Amps):
I = (kVA × 1000) / (√3 × V)
1-Phase Full Load Current (Amps):
I = (kVA × 1000) / V
- kVA: Transformer apparent power rating (Kilovolt-Amperes).
- V: Line-to-Line Voltage (Primary High Side or Secondary Low Side).
- √3: Constant factor for 3-phase power (~1.732).